7120BEP Super Explosion-Proof Strobe (120 VAC) – TOMAR Industrial

7120BEP Super Explosion-Proof Strobe (120 VAC)

  • SKU:
  • Regular price MSRP:
  • YOUR PRICE:

PRODUCT OVERVIEW

The model 7120BEP family is designed, tested, and certified for use in hazardous locations and hostile environments classified by the NEC as Class I, Div. 1 & 2, Groups C & D, Class II, Div. 1 & 2, Groups E, F, G, and Class III, Div. 1 & 2. They also meet NEMA standards 3, 4, 4X, 7CD, and 9EFG and are marine rated for use in salt water environments.

Design features include housing made of die cast high strength copper-free aluminum alloy with a baked powder epoxy finish, stainless steel hardware, oring sealed prestressed glass globe with double pitch acme threads for smooth assembly and ease of maintenance, a flash circuit, and an optional guard which need not be removed for re-lamping.

Key Features

  • NEMA 4X
  • Meets UL1203 & UL1638
  • Built-in flash
  • Xenon strobe lamp
  • Available in amber, blue, clear, green, purple (violet), and red
  • Two-year warranty on power supply
  • One-year warranty on lamp

Specifications

  • Lamp Type: 6001 Xenon strobe lamp
  • Flash Rate: 80 flashes per minute
  • Light Output: 890 effective candlepower (ECP)*
  • Voltage and Amperage: 120VAC 60 Hz draws 1.0A (1.7A max)
  • Power Supply Output: 26 watts (20 joules per flash, 2,000,000 Peak Candlepower**)
  • Operating Temperature: -40º C to +65º C
  • Temperature Code: T6 – All voltage and temperature ranges
  • Size and Weight: 12” tall x 8.75” dia. x 13 lbs

Models

Model Description Voltage
7120BEP–PMX pendant mount, 3/4” hubs 120VAC
7120BEP–FMX flange mount, 3/4” hubs 120VAC
7120BEP–WMX wall mount, 3/4” hubs 120VAC

Architect and Engineer Specifications

Visual signaling beacon shall be Tomar model number series 7120BEP or approved equal. The beacon shall be UL Listed Class I, Division 1, Groups C and D; Class II, Division 1, Groups E, F and G; and Class III for use in specified hazardous locations and /or combustible atmospheres as classified by the National Electric Code. The warning beacon shall have a 26 watt power supply and generate 20 joules per flash. Light intensity shall be 890 effective candlepower, and the light source shall be a plug-in field replaceable double-flash xenon strobe lamp operating at 80 flashes per minute. The warning signal must have built-in RFI filters to protect against radio interference and spike voltages. Beacon must have a built-in flash circuit, and voltage range shall 120VAC. Strobe beacon must meet UL 1203, and UL 1638, standards. Beacon must be rated NEMA 4X, with housing made of die cast high-strength copper-free aluminum alloy with baked powder epoxy finish, stainless steel hardware, O-ring sealed pre-stressed globe with double pitch acme threads for smooth assembly and ease of maintenance. Must include a Lexan® inner lens and tempered glass outer dome. The housing must be designed to accommodate a dome guard.